straight-through cable to connect the controller to a MDI Compliant Hub or Switch.
Alternatively, you may use a crossover cable to connect your controller directly to a PC,
which is useful for commissioning purposes. Use only Category 5 (STP CAT5) shielded
twisted-pair Ethernet cables. For strain relief, secure your Ethernet cable to the controller
with the tie wraps included in the kit using the holes in the bottom controller flange.
4 SHLD
4 SHLD

Figure 2-22 Ethernet Communications Option without Adaptor Board

If you would rather wire your UDC to your Ethernet connection without using the
Ethernet Adaptor Board, then Figure 2-22 and Table 2-8 show the connections for a
UDC to a MDI Compliant Hub or Switch utilizing a straight-through cable or for
connecting a UDC to a PC utilizing a crossover cable.
3/07
COMMUNICATION MASTER
COMMUNICATION MASTER
SHLD
SHLD
24 RXD +
24 RXD +
25 RXD -
25 RXD -
26 TXD +
26 TXD +
27 TXD -
27 TXD -
Do not run the communications lines in the same conduit as AC
Do not run the communications lines in the same conduit as AC
1
1
power. Direct connection to a PC may require the use of an
power. Direct connection to a PC may require the use of an
Ethernet cross-over cable.
Ethernet cross-over cable.
2
2
Use Shielded twisted-pair, Category 5 (STP CAT5) Ethernet cable.
Use Shielded twisted-pair, Category 5 (STP CAT5) Ethernet cable.
Maximum Distance 330 Ft.
Maximum Distance 330 Ft.
Use Switch rather than Hub to maximize performance.
Use Switch rather than Hub to maximize performance.
3
3
4 Ethernet Communications is mutually exclusive with the Second Current
4 Ethernet Communications is mutually exclusive with the Second Current
4 Ethernet Communications is mutually exclusive with the Second Current
Output.
Output.
Output.
UDC3500 Universal Digital Controller Product Manual
3
3
TXD -
TXD -
TXD +
TXD +
RXD -
RXD -
RXD +
RXD +
1
1
2
2