Honeywell UDC3500 Product Manual page 418

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Modbus Read, Write and Override Parameters plus Exception Codes
Parameter
Description
Changing the Input Type will result in the loss of Field Calibration values and will restore the
Factory Calibration values.
Input 1
169
Transmitter
Characterization
Input 1 High
29
Range Value
Input 1 Low
30
Range Value
Input 1 Ratio
106
Input 1 Bias
107
Input 1 Filter
42
Burnout (Open
164
Circuit
Detection)
Emissivity
23
402
Register
Address
ID
Hex
Decimal
00A9
169
001D
029
001E
030
006A
106
006B
107
002A
042
00A4
164
0017
023
UDC3500 Universal Digital Controller Product Manual
Data
Access
Type
INT
R/W
FP
R/W
FP
R/W
FP
R/W
FP
R/W
FP
R/W
INT
R/W
FP
R/W
Data Range or
Enumerated Selection
0 = B TC
1 = E TC H
2 = E TC L
3 = J TC H
4 = J TC M
5 = J TC L
6 = K TC H
7 = K TC M
8 = K TC L
9 = NNM H
10 = NNM L
11 = Nicrosil H TC
12 = Nicrosil L TC
13 = Plat H
14 = Plat L
15 = R TC
16 = S TC
17 = T TC H
18 = T TC L
19 = W TC H
20 = W TC L
21 = 100 PT RTD
22 = 100 PT LO RTD
23 = 200 PT RTD
24 = 500 PT RTD
25 = 1000PT
26 = Radiamatic RH
27 = Radiamatic RI
28 = Linear
29 = Square Root
–999. to 9999.
Engineering Units (Linear
types only)
–999 to 9999.
Engineering Units (Linear
types only)
–20.00 to 20.00
–999 to 9999.
Engineering Units
0 to 120 seconds
0 = None and Failsafe
1 = Upscale
2 = Downscale
3 = No Failsafe
0.01 to 1.00
3/07