Setting The Thresholds For The Operating Time; Setting The Thresholds For Excesssive Fault Frequency - GE MiCOM P40 Agile Technical Manual

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P14D
5.1.3

SETTING THE THRESHOLDS FOR THE OPERATING TIME

Slow CB operation indicates the need for mechanism maintenance. Alarm and lockout thresholds (CB Time Maint
and CB Time Lockout) are provided to enforce this. They can be set in the range of 5 to 500 ms. This time relates to
the interrupting time of the circuit breaker.
5.1.4

SETTING THE THRESHOLDS FOR EXCESSSIVE FAULT FREQUENCY

Persistent faults will generally cause autoreclose lockout, with subsequent maintenance attention. Intermittent
faults such as clashing vegetation may repeat outside of any reclaim time, and the common cause might never be
investigated. For this reason it is possible to set a frequent operations counter, which allows the number of
operations Fault Freq Count over a set time period Fault Freq Time to be monitored. A separate alarm and lockout
threshold can be set.
P14D-TM-EN-8
Chapter 14 - Monitoring and Control
293