Thermal Overload Protection Implementation; Thermal Overload Protection Logic; Application Notes; Setting Guidelines For Dual Time Constant Characteristic - GE MiCOM P40 Agile Technical Manual

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Chapter 6 - Current Protection Functions
12.3

THERMAL OVERLOAD PROTECTION IMPLEMENTATION

The device incorporates a current-based thermal characteristic, using RMS load current to model heating and
cooling of the protected plant. The element can be set with both alarm and trip stages.
Thermal Overload Protection is implemented in the THERMAL OVERLOAD column of the relevant settings group.
This column contains the settings for the characteristic type, the alarm and trip thresholds and the time constants.
12.4

THERMAL OVERLOAD PROTECTION LOGIC

IA
IA
IB
IB
IC
IC
Thermal Trip
Characteristic
Disabled
Single
Dual
Time Constant 1
Time Constant 2
Reset Thermal
Thermal Alarm
V00630

Figure 55: Thermal overload protection logic diagram

The magnitudes of the three phase input currents are compared and the largest magnitude is taken as the input
to the thermal overload function. If this current exceeds the thermal trip threshold setting a start condition is
asserted.
The Start signal is applied to the chosen thermal characteristic module, which has three outputs signals; alarm trip
and thermal state measurement. The thermal state measurement is made available in one of the MEASUREMENTS
columns.
The thermal state can be reset by either an opto-input (if assigned to this function using the programmable
scheme logic) or the HMI panel menu.
12.5

APPLICATION NOTES

12.5.1

SETTING GUIDELINES FOR DUAL TIME CONSTANT CHARACTERISTIC

The easiest way of solving the dual time constant thermal equation is to express the current in terms of time and
to use a spreadsheet to calculate the current for a series of increasing operating times using the following
equation, then plotting a graph.
(
2
0 4
.
.
I e
=
p
I
0 4
.
122
Max RMS
Thermal
Calculation
445
)
(
)
τ
τ
+
t
/
1
t
/
2
2
0 6
.
.
I e
k I
p
(
)
(
)
τ
− −
t / τ 2
+
/
1
t
e
0 6
.
e
1
Thermal trip
threshold
2
2
.
FLC
Thermal State
680
Thermal Trip
785
Thermal Alarm
P14D-TM-EN-8
P14D

Advertisement

Table of Contents
loading

Table of Contents