GE MiCOM P40 Agile Technical Manual page 117

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P14D
Chapter 6 - Current Protection Functions
Example
If the overcurrent device has a setting of 160% In, but the minimum fault current for the remote fault condition is
only 80% In, then the required k factor is given by:
0 8
.
k =
=
0 42
.
×
1 6 1 2
.
.
The voltage threshold, Vdep OC V< setting would be set below the lowest system voltage that may occur under
normal system operating conditions, whilst ensuring correct detection of the remote fault.
P14D-TM-EN-8
91

Advertisement

Table of Contents
loading

Table of Contents