P14D
Chapter 17 - Communications
RSTP can recover network faults quickly, but the fault recovery time depends on the number of devices on the
network and the network topology. A typical figure for the fault recovery time is 300ms. Therefore, RSTP cannot
achieve the "bumpless" redundancy that some other protocols can.
Refer to IEEE 802.1D 2004 standard for detailed information about the opration of the protocol.
5.5

CONFIGURING IP ADDRESS

The redundant Ethernet facility does not have any special IP address configuration requirements. There is just one
IP address for the device, which can be configured using the IEC61850 configurator as for a standard Ethernet
device.
The IED configurator will automatically display the PRP/HSR configuration parameters.
P14D-TM-EN-8
353