Ring Main Arrangements; Setting Guidelines; Figure 24: Typical Ring Main With Associated Overcurrent Protection - GE MiCOM P40 Agile Technical Manual

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Chapter 6 - Current Protection Functions
3.5.2

RING MAIN ARRANGEMENTS

E00604

Figure 24: Typical ring main with associated overcurrent protection

In a ring main arrangement, current may flow in either direction through the various device locations, therefore
directional overcurrent devices are needed to achieve correct discrimination.
The normal grading procedure for overcurrent devices protecting a ring main circuit is to consider the ring open at
the supply point and to grade the devices first clockwise and then anti-clockwise. The arrows shown at the various
device locations depict the direction for forward operation of the respective devices (i.e. the directional devices are
set to look into the feeder that they are protecting).
The diagram shows typical time settings (assuming definite time co-ordination is used), from which it can be seen
that any faults on the interconnections between stations are cleared discriminatively by the devices at each end of
the feeder.
Any of the overcurrent stages may be configured to be directional and co-ordinated, but bear in mind that IDMT
characteristics are not selectable on all the stages.
3.5.3

SETTING GUIDELINES

Standard principles should be applied in calculating the necessary current and time settings. The example detailed
below shows a typical setting calculation and describes how the settings are applied.
86
2.1s
51
0.1s
F
67
67
Load
1.7s
0.5s
67
Load
1.3s
E
67
0.9s
67
Source
A
2.1s
51
0.1s
Load
67
Load
67
Load
67
1.3s
Load
67
0.9s
67
D
B
1.7s
0.5s
C
P14D-TM-EN-8
P14D

Advertisement

Table of Contents
loading

Table of Contents