P14D
2.5
REAR ETHERNET PORT COPPER
Main Use
Communication protocol
Connector
Cable type
Isolation
Supported Protocols
Constraints
2.6
REAR ETHERNET PORT - FIBRE
Main Use
Connector
Communication protocol
Fibre type
Supported Protocols
Wavelength
2.6.1
100 BASE FX RECEIVER CHARACTERISTICS
Parameter
Input Optical Power Minimum at
Window Edge
Input Optical Power Minimum at
Eye Center
Input Optical Power Maximum
Conditions: TA = 0°C to 70°C
2.6.2
100 BASE FX TRANSMITTER CHARACTERISTICS
Parameter
Output Optical Power BOL 62.5/125 µm
NA = 0.275 Fibre EOL
Output Optical Power BOL 50/125 µm
NA = 0.20 Fibre EOL
Optical Extinction Ratio
Output Optical Power at Logic "0" State
Conditions: TA = 0°C to 70°C
P14D-TM-EN-8
Rear Ethernet port using CAT 5/6/7 wiring
Substation Ethernet communications
10BaseT/100BaseTX
RJ45
Screened twisted pair (STP)
1 kV
IEC 61850, DNP3.0 OE
Maximum cable length 100 m
Rear Ethernet port using fibre-optic cabling
Sym
Min.
PIN Min. (W)
PIN Min. (C)
PIN Max.
-14
Sym
Min.
-19
PO
-20
-22.5
PO
-23.5
PO
Chapter 22 - Technical Specifications
IEC 61850 or DNP3 OE SCADA communications
UNI SONET OC-3 LC (1 each for Tx and Rx)
100 BaseFX
Multimode 50/125 µm or 62.5/125 µm
IEC 61850, DNP3.0 OE
1300 nm
Typ.
-33.5
-34.5
-11.8
Typ.
-16.8
-20.3
Max.
Unit
–31
dBm avg.
-31.8
Bm avg.
dBm avg.
Max.
Unit
-14
dBm avg.
-14
dBm avg.
10
%
-10
dB
-45
dBm avg.
471