Application Notes; Undervoltage Setting Guidelines - GE MiCOM P40 Agile Technical Manual

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Chapter 10 - Voltage Protection Functions
2.3

APPLICATION NOTES

2.3.1

UNDERVOLTAGE SETTING GUIDELINES

In most applications, undervoltage protection is not required to operate during system earth fault conditions. If this
is the case you should select phase-to-phase voltage measurement, as this quantity is less affected by single-
phase voltage dips due to earth faults.
The voltage threshold setting for the undervoltage protection should be set at some value below the voltage
excursions that may be expected under normal system operating conditions. This threshold is dependent on the
system in question but typical healthy system voltage excursions may be in the order of 10% of nominal value.
The same applies to the time setting. The required time delay is dependent on the time for which the system is able
to withstand a reduced voltage.
If motor loads are connected, then a typical time setting may be in the order of 0.5 seconds.
190
P14D
P14D-TM-EN-8

Advertisement

Table of Contents
loading

Table of Contents