Figure 118: Transient Voltage Vector Change Q Due To Change In Load Current Idl - GE MiCOM P40 Agile Technical Manual

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P14D
Chapter 10 - Voltage Protection Functions
E
I X
L
V
T
I R
L
θ
I
L
V
∆I X
T
L
∆I
L
E00873
Figure 118: Transient voltage vector change q due to change in load current ID
L
The voltage vector shift function is designed to respond within one to two full mains cycles when its threshold is
exceeded. Discrimination between a loss of mains condition and a circuit fault is therefore achievable only by
selecting the angle threshold to be above expected fault levels. This setting can be quantified by calculating the
angular change due to islanding. However, this angular change depends on system topology, power flows and
very often also on the instant of the system faults. For example a bolted three phase short circuit which occurs
close to the relay may cause a problem in that it inherently produces a vector shift angle at the instant of the fault
which is bigger than any normal setting, independent of the mains condition. This kind of fault would cause the
relay to trip shortly after the instant of its inception. Although this may seem to be a disadvantage of the vector
shift function, isolating the embedded generator at the instant of a bolted three phase fault is of advantage to the
PES. This is because the mains short circuit capacity and consequently the energy feeding the short circuit is
limited by the instant operation of the relay. The fast operation of this vector shift function renders it to operate at
the instant of a disturbance rather than during a gradual change caused by a gradual change of power flow.
Operation can occur at the instant of inception of the fault, at fault clearance or following non-synchronized
reclosure, which affords additional protection to the embedded generator.
P14D-TM-EN-8
213

Advertisement

Table of Contents
loading

Table of Contents