P14D
Communication set-up (COM port, Baud rate, or Framing) is not correct
●
Transaction values are not suitable for the IED or the type of connection
●
The connection cable is not wired correctly or broken
●
The option switches on any protocol converter used may be incorrectly set
●
3.7.1
DIAGRAM RECONSTRUCTION
Although a scheme can be extracted from an IED, a facility is provided to recover a scheme if the original file is
unobtainable.
A recovered scheme is logically correct but much of the original graphical information is lost. Many signals are
drawn in a vertical line down the left side of the canvas. Links are drawn orthogonally using the shortest path from
A to B. Any annotation added to the original diagram such as titles and notes are lost.
Sometimes a gate type does not appear as expected. For example, a single-input AND gate in the original scheme
appears as an OR gate when uploaded. Programmable gates with an inputs-to-trigger value of 1 also appear as
OR gates
3.7.2
PSL VERSION CHECK
The PSL is saved with a version reference, time stamp and CRC check (Cyclic Redundancy Check). This gives a
visual check whether the default PSL is in place or whether a new application has been downloaded.
3.8
REPAIR AND MODIFICATION PROCEDURE
Please follow these steps to return an Automation product to us:
1.
Get the Repair and Modification Return Authorization (RMA) form
An electronic version of the RMA form is available from the following web page:
www.gegridsolutions.com/contact
2.
Fill in the RMA form
Fill in only the white part of the form.
Please ensure that all fields marked (M) are completed such as:
Equipment model
○
Model No. and Serial No.
○
○
Description of failure or modification required (please be specific)
Value for customs (in case the product requires export)
○
Delivery and invoice addresses
○
Contact details
○
3.
Send the RMA form to your local contact
For a list of local service contacts worldwide,visit the following web page:
www.gegridsolutions.com/contact
P14D-TM-EN-8
Chapter 21 - Maintenance and Troubleshooting
465