P14D
CB Fail Alarm
Remove IN> Start
Enabled
Disabled
IN1>1 Start
IN1>2 Start
IN1>3 Start
IN1>4 Start
IN2>1 Start
IN2>2 Start
IN2>3 Start
IN2>4 Start
ISEF>1 Start
ISEF>2 Start
ISEF>3 Start
ISEF>4 Start
V00649
Figure 60: Blocked Earth Fault logic
The IN/SEF>Blk Start signal is derived from the logical OR of the phase overcurrent start outputs. This output is
then gated with the CB Fail Alarm DDB signal and the Remove IN> Start setting.
14.4
APPLICATION NOTES
14.4.1
BUSBAR BLOCKING SCHEME
E00636
Figure 61: Simple busbar blocking scheme
P14D-TM-EN-8
&
&
1
Incomer
IED
O/P
CB
from
fail
start
backtrip
contact
Feeder 1
Feeder 2
Chapter 6 - Current Protection Functions
1
Block highset element
IED
CB fail backtrip
IED
IED
Feeder 3
Feeder 4
IN/SEF>Blk Start
IED