Table 2-10
Firepower 82xx Family and Firepower and AMP 83xx Family Physical and Environmental Parameters
Parameter
Fiber 10GBASE
non-bypass
MMSR or SMLR NetMod
Fiber 1000BASE-SX
non-bypass NetMod
Power supply
Operating temperature
Non-operating
temperature
Operating humidity
Non-operating humidity
Altitude
Cooling requirements
Description
Quad-port fiber non-bypass interfaces with LC connectors
Cable and distance:
LR is single-mode at 5000 m (available)
SR is multimode fiber (850 nm) at 550 m (standard)
Quad-port fiber non-bypass interfaces 1000BASE-SX with LC connectors
Cable and distance:
SX is multimode fiber (850 nm) at 550 m (standard)
82xx Family:
Dual 750 W redundant power supplies designed for AC or DC.
AC Voltage: 100 VAC to 240 VAC nominal (85 VAC to 264 VAC
AC Current: 8A maximum over the full range, per supply
AC Frequency range: 47 Hz to 63 Hz
DC Voltage: -48 VDC nominal referenced to RTN
DC Current: 18A maximum, per supply
83xx Family:
Dual 1000 W redundant power supplies designed for AC or DC.
AC Voltage: 100 VAC to 240 VAC nominal (85 VAC to 264 VAC
AC Current: 11A maximum over the full range, per supply
AC Frequency range: 47 Hz to 63 Hz
DC Voltage: -48 VDC nominal referenced to RTN
DC Current: 25A maximum, per supply
82xx Family:
50°F to 95°F (10°C to 35°C)
83xx Family:
41°F to 104°F (5°C to 40°C)
o
o
o
-29
F to 158
F (-20
C to 70
5% to 85% non-condensing
5% to 90%, non-condensing with a maximum wet bulb of 82°F (28°C) at temperatures from 77°F
to 95°F (25°C to 35°C)
0 ft (sea level) to 6000 ft (0 to 1800 m)
up to 2900 BTU/hour
You must provide sufficient cooling to maintain the appliance within its required operating
temperature range. Failure to do this may cause a malfunction or damage to the appliance.
maximum)
4A maximum for 187 VAC to 264 VAC, per supply
-40 VDC to -72 VDC maximum
maximum)
5.5A maximum for 187 VAC to 264 VAC, per supply
-40 VDC to -72 VDC maximum