Programming Site Data
Selecting the Alarm Type (cont.)
4. Do one of the following:
If you are using a 1-Channel meter and selected
high or low, proceed to Step 7.
fault, proceed to Step 9.
If you are using a 2-Channel meter, proceed to the next step.
5. Use the pull-down menu to select the desired channel option and
press Next Item/Enter.
6. Do one of the following:
high or low, proceed to Step 7.
fault, proceed to Step 9.
7. Use the pull-down menu to select the desired measurement
parameter and press Next Item/Enter. See Table 1-10 below for a
description of the available options.
Table 1-10: Output Measurement Options
Forward Totalized Volume Flow
Reverse Totalized Volume Flow
Total Flow Measurement Time
Forward Totalized Mass Flow
Reverse Totalized Mass Flow
Diagnostic Parameters*
DIAG*
The
option listed above represents all of the individual
diagnostic parameters that appear at the previous prompt. See
Chapter 3, Diagnostics, of the Service Manual for a complete
description of these options.
Note: The measurement units that appear in these prompts are those
Global-System
selected in the
8. Enter a value for the trigger point of the alarm and press Next
Item/Enter. Go to Procedure Options on the following page.
9. Use the pull-down menu to select the type of error (flow, non-flow
or both) that will trigger the fault alarm and press Next Item/
Enter.
Options
Flow Velocity
Volumetric Flow
Mass Flow
window earlier in this section.
November 2004
1-31