Setting Up Slot 0 and Slot 1
Input/Outputs
Analog Outputs
Setting Up Output Scale
1-26
The Model XGS868 has two built-in analog outputs, which are
Slot 0
assigned to
. Also, a variety of input/output option cards may be
Slot 1
installed in
. See Chapter 1, Installation, of the Startup Guide for
a complete description of the available option cards.
To set up option cards, refer to one of the following sections:
Analog Outputs - refer to section below.
Analog Inputs - see page 1-28
RTD Inputs - see page 1-29
Alarm Relays - see page 1-30
Totalizer Outputs - see page 1-32
Frequency Outputs - see page 1-34
While following the programming instructions, refer to Figure A-4 in
Appendix A.
Accessing the Output
1. Open the SITE EDIT MENU from the Edit Functions menu.
2. Select Global.
3. Select Input/Output.
4. Select Options.
5. Select Slot 0 or Slot 1 depending on which output you want to set
up.
6. Use the pull-down menu to select the desired output and press
Next Item/Enter.
Note: Output letters (A, B, etc.) correspond to the output wiring
terminal numbers from top to bottom. For example, Output A
corresponds to pins 1,2 and 3; Output B corresponds to pins 4,
5 and 6; etc.
1. Use the pull-down menu to select the desired output scale and
press Next Item/Enter.
2. Do one of the following:
If you selected Off, IDM returns to the Input/Output window.
Go to Procedure Options on the next page.
If you selected 0-20 mA or 4-20 mA, and are using a
1-Channel meter, proceed to Step 4.
2-Channel meter, proceed to the next step.