RTD Inputs
Procedure Options
Programming Site Data
Option cards with RTD inputs have a temperature range of –100° to
350°C. While following the programming instructions, refer to
Figure A-4 in Appendix A.
Complete the following steps to set up the RTD inputs of an option
card installed in Slot 1:
Accessing the Input
1. Open the SITE EDIT MENU from the Edit Functions menu.
2. Select Global.
3. Select Input/Output.
4. Select Options.
5. Select Slot 1.
6. Use the pull-down menu to select the desired input and press Next
Item/Enter.
Note: Input letters (A, B, etc.) correspond to the input wiring
terminal numbers from top to bottom. For example, Input A
corresponds to pins 1, 2 and 3; Input B corresponds to pins 4,
5 and 6; etc.
Setting Up the RTD Input
1. Enter a label for the RTD input and press Next Item/Enter.
2. Use the pull-down menu to select the desired input type and Next
Item/Enter. Do one of the following:
Off
If
was selected, go to Procedure Options below.
Temperature
If
was selected, proceed to the next step.
3. Enter a temperature value for the low end of the analog input
range and press Next Item/Enter.
4. Enter a temperature value for the high end of the analog input
range and press Next Item/Enter.
After completing the above steps, IDM returns to the Input/Output
window. Do one of the following:
To continue programming, refer to Appendix A, Menu Maps
for IDM, to navigate to the desired menu.
To leave the User Program, press Exit Page three times.
November 2004
1-29