Mitsubishi QD51 Programming Manual page 665

Logic controller
Hide thumbs Also See for QD51:
Table of Contents

Advertisement

APPENDIX
Numbers in the B00
range • • • Errors related to communication with the PLC CPU
H
Error code
B10
A station with the specified PC number does not
H
exist.
B11
Communication error between the
H
communication module and PLC CPU.
B12
A special function module cannot be found at
H
the specified I/O address.
B13
A step number (address) exceeding the
H
parameter range is specified.
B18
A remote RUN/STOP was executed from
H
another module.
B20
The MELSECNET (II) is not operating correctly.
H
B21
Cannot access the specified special function
H
module.
B40
Time out error
H
B41
Data communication error with the CPU
H
B46
The specified CPU is faulty.
H
B80
The contents of the control table for the PCRD
H
and PCWT instructions are incorrect.
The data storage area is too small.
B81
It is attempted to execute processing that the
H
specified CPU cannot perform.
B82
Device name (device code) is incorrect.
H
B83
Device number is incorrect.
H
B84
It is attempted to monitor before performing
H
monitor registration.
B85
The PC number is different from at the time of
H
monitor registration.
B86
The system configuration is different from at the
H
time of monitor registration.
B87
There are too many points to be monitored.
H
B88
Cannot be executed in the specified block
H
number of the extension file registers.
B89
It is attempted to change a program or
H
parameters while the ROM is operating.
B8A
It is attempted to perform a processing that
H
cannot be performed while the CPU is running.
B8D
A processing code for the PCRD and PCWT
H
instructions is incorrect.
BA4
An error that occurred in the CPU was returned
H
to the PCRD/PCWT instruction.
BA7
An error that occurred in the intelligent
H
communication module was returned to the
PCRD/PCWT instruction.
BAC
An error that occurred in Ethernet was returned
H
to the PCRD/PCWT instruction.
BAF
An error that occurred in the network module
H
was returned to the PCRD/PCWT instruction.
App - 20
Meaning
Corrective action
Check the specified station.
Check the communication module or CPU.
Check the special function module at the specified
address.
Specify a step number (address) within the parameter
range.
Cancel the remote RUN/STOP from the other
module.
Check the MELSECNET (II).
Check to see if the special function module has failed.
Check the CPU.
Check to see if there is a CPU error.
Check to see if there is a CPU error.
Check the contents of the control table.
Increase the data storage area.
The specified processing cannot be performed in the
applicable CPU.
Specify the correct device code.
Specify a device number in the allowable range.
Monitor after performing monitor registration.
Use the same PC number as at the time of monitor
registration.
Use the same system configuration as at the time of
monitor registration.
Decrease the number of monitoring points.
Change to extension file registers where the
execution is possible.
Do not change programs or parameters while the
ROM is operating.
Perform the processing after stopping the CPU.
Specify the processing code correctly.
Check the detailed error code using the format 2
control table of the PCRD/PCWT instruction. See the
manual for the CPU that was accessed or the CPU
that was routed through prior to the accessed CPU
for the meaning and corrective action for the detailed
error code.
Check the detailed error code using the format 2
control table of the PCRD/PCWT instruction. See the
error code table in Appendix for the meaning and
corrective action for the detailed error code.
Check the detailed error code using the format 2
control table of the PCRD/PCWT instruction. See the
manual for the Ethernet module that was routed
through prior to the access target for the meaning and
corrective action for the detailed error code.
Check the detailed error code using the format 2
control table of the PCRD/PCWT instruction. See the
manual for the network module that was routed
through prior to the access target for the meaning and
corrective action for the detailed error code.
MELSEC-Q
App - 20

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ad51h-s3Qd51-r24A1sd51s

Table of Contents