11 INSTRUCTIONS AND FUNCTIONS
11 - 337
Format 3 control table
%(0)
• • • • • •
Format 3 control table
%(1)
• • • • • •
Specify the network number of the network to be accessed.
See Section 4.2.2 for the allowable specification range.
%(2)
• • • • • •
Specify the station number of the PLC CPU to which data is
to be written.
See Section 4.2.2 for the allowable specification range.
%(3)
• • • • • •
Detailed error codes are stored here.
See Appendix 4.4.2 for the details about the error codes.
%(4)
• • • • • •
Processing code
%(5)
• • • • • •
Specify the requested CPU.
%(6)
• • • • • •
Specify the starting I/O number of the intelligent functional
module to whose buffer memory data is to be written.
%(7)
• • • • • •
Specify the address (lower) of buffer memory to which data
is to be written.
%(8)
• • • • • •
Specify the address (higher) of buffer memory to which
data is to be written.
%(9)
• • • • • •
Specify the number of bytes of data to be written, including
the specified intelligent functional module's buffer memory
address.
The allowable specification range is as follows:
• Q series CPU
• QnA series CPU
• Specify 257 (&H101).
• Specify 533 (&H215).
• PLC No.1
• • • • • • 992 (&H3E0)
• PLC No.2
• • • • • • 993 (&H3E1)
• PLC No.3
• • • • • • 994 (&H3E2)
• PLC No.4
• • • • • • 995 (&H3E3)
• Control PLC
• • • • • • 1023 (&H3FF)
1 to 1920 bytes
1 to 960 bytes
MELSEC-Q
11 - 337