Configuration 410 - Sensorless Field-Oriented Control - BONFIGLIOLI Active ACT 201-05 Brief Manual

230 v / 400 v 0.55 kw ... 30.0 kw
Table of Contents

Advertisement

5.6.2.2
Configuration 410 contains the functions for sensorless, field-oriented control of a 3-
phase machine. The current motor speed is determined from the present currents
and voltages in combination with the machine parameters. Separate control of torque
and flux-forming current enables high drive dynamism at a high load moment.
32
32
Configuration 410 –
Sensorless Field-Oriented Control
X210A
1
+20 V/180 mA
GND 20 V
2
3
S1IND
S2IND
4
5
S3IND
6
S4IND
7
S5IND
M
X210B
1
S6IND
GND 20 V
2
-
+
3
S1OUT
-
+
MFO1A
V
4
5
+10 V/4 mA
MFI1A
6
GND 10 V
7
Control terminal X210A
X210A.1
Supply voltage +20V
X210A.2
Ground 20 V
X210A.3
Controller release / error acknowl-
edgment
X210A.4
Start of clockwise operation
X210A.5
Start of anticlockwise operation
X210A.6
Data set change-over 1
X210A.7
Data set change-over 2
Control terminal X210B
X210B.1
Motor thermal contact
X210B.2
Ground 20 V
X210B.3
Operating message
X210B.4
Analog signal of actual frequency
X210B.5
Supply voltage +10V
Reference value potentiometer
X210B.6
Reference speed 0 ...+10 V
X210B.7
Ground 10 V
06/05
06/05

Hide quick links:

Advertisement

Table of Contents
loading