The parameters to be configured during the guided commissioning were selected
from common applications and can be supplemented as required by further settings
in the PARA menu branch. The parameters and basic software functions linked to the
corresponding actual value are documented in the operating instructions.
36
36

Parameter Menu (PARA)

A
B
A
Use the arrow keys to select the required number from the parameters
displayed in numerical order. The parameter number is displayed with the
active data set (flashes).
In the current data set, the related parameters are displayed, including the
corresponding data set number. The seven-segment display shows data set 0 if
the parameter values in the four data sets are identical.
+
Change to the last parameter edited.
FUN ,
Display of last parameter (highest number).
FUN ,
Display of first parameter (lowest number).
Use the ENT key to select the parameter. The parameter is displayed including
B
its value, unit and the active data set. If settings are edited in data set 0, the
parameter values are changed in the four data sets.
Use the arrow keys to adjust the parameter value or to select an operation
C
mode. The adjustment possibilities you have depend on the parameter.
Keep the arrow keys pressed for a while to change the displayed values quickly.
If you release the keys again, the speed at which the values change is reduced
again.
If the parameter value starts to flash, the speed at which the values change is
reset to the initial value again.
+
Set parameter to factory setting.
FUN ,
Set parameter to highest value.
FUN ,
Set parameter to smallest value.
Change of the data set in the case of data set related
FUN , ENT
parameters.
D
Use the ENT key to save the parameter. For a short time, the message SEt
including the parameter number and the data set is displayed.
To leave the parameter unchanged, press the ESC key.
Err1: EEPrO
Parameter has not been saved.
Parameter can only be read (i.e. not edited) when the unit is in
Err2: StOP
operation.
Err3: Error
Other error
E
After saving the parameter, you can edit the value again or return to the
parameter selection menu by pressing the ESC key.
ESC
E
ENT
C
Keys
Keys
Messages
ENT
D
ESC
06/05
06/05