The warning and error messages displayed during the verification process have to be
observed. If a critical condition is detected during the guided commissioning, it is
displayed by the control unit. Depending on the deviation from the expected
parameter value, either a warning or an error message is displayed.
−
−
If an error message is displayed, the rated values must be checked and corrected.
The guided commissioning procedure is repeated until the rated values have been
entered correctly. Aborting the guided commissioning procedure by pressing ESC key
should only be done be expert users because it may be possible that rated values
have not been entered or determined correctly.
42
42
To ignore the warning or error messages, press the ENT key. The guided
commissioning is continued. However, it is recommended that the data be
checked and corrected if necessary.
To correct the entered parameter values after the warning or error message,
press the ESC key. Use the arrow keys to switch to the parameter value which is
to be corrected.
Code
No warning message present. This message can be read out via an
SA000
optional communication module.
The value of the parameter
SA001
range of the frequency inverter. The maximum reference voltage is
indicated on the nameplate of the frequency inverter.
The calculated efficiency is in the limit range for a three-phase motor.
Check the values entered for the parameters
SA002
Current
371 and
The value entered for parameter
SA003
normal range (0.6 to 0.95). Check the value.
The calculated slip for an asynchronous motor is in the limit range.
Check the values entered for parameters
SA004
Frequency
375.
Code
SF000
No error message exists
The value entered for parameter
SF001
value.
The value for parameter
Rated Mech. Power
SF002
parameters
values.
The value entered for parameter
SF003
than 1 or smaller than 0.3). Correct the value.
The calculated slip frequency is negative. Correct the values entered for
SF004
Rated Speed
parameters
The calculated slip frequency is too high.
Correct the values entered for parameters
SF005
Frequency
375.
The calculated total output of the drive is lower than the rated power.
SF006
Correct the value entered for parameter
The set configuration is not supported by the guided commissioning. For
Configuration
SF007
parameter
these operating instructions.
Warning Messages
Measures / Remedy
Rated Voltage
Rated Mech. Power
376.
Rated Cosinus Phi
Error Messages
Measures / Remedy
Rated Current
Rated Current
376 and
Rated Cosinus Phi
Rated Frequency
372 and
Rated Mech. Power
30, select one of the configurations described in
370 is out of the rated voltage
Rated Voltage
370,
374 is outside of the
Rated Speed
372 and
371 is too low. Correct the
371 is too high, referred to
Rated Voltage
370. Correct the
374 is wrong (greater
375.
Rated Speed
372 and
376.
Rated
Rated
Rated
06/05
06/05