BONFIGLIOLI Active ACT 201-05 Brief Manual page 50

230 v / 400 v 0.55 kw ... 30.0 kw
Table of Contents

Advertisement

Rated Mech. Power
asynchronous motor.
Setting:
Switching Frequency
defined at a switching frequency of 2 kHz. Higher switching frequencies require a
reduction of the output current (see technical data).
Setting:
Min. Switching Frequency
is reduced automatically in the case of a thermal overload of the frequency inverter.
Setting:
Minimum Frequency
inputs S2IND, S3IND results in an acceleration of the drive to the minimum
frequency.
Setting:
Maximum Frequency
output frequency of the frequency inverter.
Setting:
Acceleration (Clockwise)
how fast the output frequency is changed after a start, stop or brake command or
when the reference value is changed.
Setting:
Operation Mode
adjusted according to the connected signal source.
Setting:
Fixed Frequency 1
fixed frequencies is effected via the fixed frequency change over function of the
multi-function input MFI1
Operation Mode
over S4IND, S5IND, the fixed frequency in one of the four data sets can be selected.
Up to 8 fixed frequencies can be parameterized and selected via the control of the
digital inputs.
Setting:
Op. Mode Digital Output 1
and monitoring functions can be assigned to the digital output S1OUT and the relay
output S3OUT.
Setting:
48
48
376 - enter the power (in kW) indicated on the type plate of the
0.1⋅P
... 10⋅P
FIN
FIN
400 - The rated operating point of the frequency inverter is
2 kHz, 4 kHz, 8 kHz, 12 kHz, 16 kHz
401 – defines the minimum value the switching frequency
2 kHz, 4 kHz, 8 kHz, 12 kHz, 16 kHz
418 - the start command entered via the control unit or digital
0.00 Hz ... 999.99 Hz
419 - The speed range of the drive is limited by the maximum
0.00 Hz ... 999.99 Hz
Deceleration (Clockwise)
420,
0.00 Hz/s ... 9999.99 Hz/s ...
452 (for multi-function input); the set point at input MFI1 can be
1 -
voltage signal, 0 V ... 10 V (factory setting)
2 -
current signal, 0 mA ... 20 mA
3 -
digital fixed frequency change-over, 0 V ... 24 V, digital input
Fixed Frequency 2
480,
452 (multi-function input on setting 3). Via the data set change-
-999.99 Hz ... 999.99 Hz
Op. Mode Digital Output 3
530,
0 -
switched off
2 -
run signal, drive turning/not turning message
3 -
fault message
11 -
Warning
41 -
trigger electro-mechanical brake
1xx -
inverted operation mode (LOW active)
421 - the ramps define
481 - change-over between the two
532 - various control
06/05
06/05

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents