7.5.6 Disable Variable Module Management System Mode from the UPS Command Menu
To disable Variable Module Management System mode:
NOTE
The Variable Module Management System mode commands are displayed only if enabled at the factory or
by an Eaton Customer Service Engineer.
The Variable Module Management System and Energy Saver System modes are mutually exclusive. If the
Energy Saver System mode is enabled, the Variable Module Management System mode commands will not
be displayed.
1.
Press the
CONTROLS
2.
On the System Status screen, select the
3.
Press the
CONTROLS
is displayed.
4.
On the UPS Control Command screen, select
5.
Press the
pushbutton on the UPS Command menu bar.
SELECT
The UPS transfers to Battery mode and then to Online mode in approximately ten seconds.
The Online status indicator is illuminated. The UPS status indicates ONLINE. The UPM status indicates
ONLINE.
7.5.7 Start Variable Module Management System High Alert Mode from the UPS Command Menu
To start High Alert mode:
NOTE
The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer
Service Engineer.
The Variable Module Management System and Energy Saver System modes are mutually exclusive. If the
Energy Saver System mode is enabled, the Variable Module Management System mode commands will not
be displayed.
1.
Press the
CONTROLS
2.
On the System Status screen, select the
3.
Press the
CONTROLS
screen is displayed.
4.
On the UPS Control Command screen, select
5.
Press the
pushbutton on the UPS Command menu bar.
SELECT
The UPS starts High Alert mode with the UPMs online supplying the critical load. After one hour the
UPS transfers to Variable Module Management System mode.
The Online status indicator is illuminated. The UPS status indicates HIGH ALERT. The UPM status
indicates ONLINE. The power module is on.
pushbutton on the main menu bar. The System Status screen is displayed.
UPS
pushbutton on the System Status menu bar. The UPS Control Command screen
pushbutton on the main menu bar. The System Status screen is displayed.
UPS
pushbutton on the System Status menu bar. The UPS Control Command
9395P 250 kVA / 275 kVA / 300 kVA
command.
DISABLE VAR MODULE MANAGEMENT
command.
.
START HIGH ALERT
User's and Installation Guide
.