Operation
Subfunction
Function
UPS Control
Commands
Go to Online
Enable (Disable) Energy Saver
Enable (Disable) Var Module
Management
Start High Alert
Go to Bypass
Load Off
Bypass
Commands
Go to Bypass
Go to Online
Enable (Disable) Energy Saver
Enable (Disable) Var Module
Management
Start High Alert
Load Off
Charger Control
Commands
Charger On
Charger Off
UPM Control
Commands
UPM On
UPM Off
UPM Go to Online
Charger On
Charger Off
NOTE The Energy Saver System and Variable Module Management System mode commands are displayed only if
enabled at the factory or by an Eaton Customer Service Engineer
NOTE Variable Module Management System and Energy Saver System modes are mutually exclusive.
Table 7-8. Command Menu
Operation
Use the up or down arrow pushbutton to highlight the command function desired,
then press the SELECT pushbutton to execute the command or proceed to further
command screens.
Starts the UPS in Online mode or transfers the UPS to Online mode from Bypass mode.
Enables or disables Energy Saver System mode. Enable changes to Disable when
the Energy Saver System mode is enabled.
Enables or disables the Variable Module Management System mode. Enable changes
to Disable when the Variable Module Management System mode is enabled.
Starts High Alert mode.
Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from Online
mode.
Displays the Load Off screen (see paragraph 7.4.7).
Use the up or down arrow pushbutton to highlight the command function desired,
then press the SELECT pushbutton to execute the command or proceed to further
command screens.
Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from Online
mode.
Starts the UPS in Online mode or transfers the UPS to Online mode from Bypass mode.
Enables or disables Energy Saver System mode. Enable changes to Disable when
the Energy Saver System mode is enabled.
Enables or disables the Variable Module Management System mode. Enable changes
to Disable when the Variable Module Management System mode is enabled.
Starts High Alert mode.
Displays the Load Off screen (see paragraph 7.4.7).
Use the up or down arrow pushbutton to highlight the command function desired,
then press the SELECT pushbutton to execute the command.
Turns the battery charger on.
Turns the battery charger off.
Use the up or down arrow pushbutton to highlight the command function desired,
then press the SELECT pushbutton to execute the command.
Turns the UPM on without transferring the load to Online mode. The Load is on
bypass.
Transfers the load to bypass and turns the UPM off.
Turns the UPM on and transfers the load to Online mode.
Turns the battery charger on.
Turns the battery charger off.
.
9395P 250 kVA / 275 kVA / 300 kVA
User's and Installation Guide