5.
Press the
pushbutton on the Bypass Command menu bar.
SELECT
If the UPS is online, the UPS transfers to Energy Saver System mode.
The Online status indicator is illuminated. The UPS status indicates ONLINE + ESS. The UPM status
indicates ONLINE. If the battery is not charging, the power module is off.
7.6.10 Disable Energy Saver System Mode from the Bypass Command Menu
To disable Energy Saver System mode:
NOTE
The Energy Saver System mode commands are displayed only if enabled at the factory or by an Eaton Customer
Service Engineer.
The Variable Module Management System and Energy Saver System modes are mutually exclusive. If the
Variable Module Management System mode is enabled, the Energy Saver System mode commands will not be
displayed.
1.
Press the
CONTROLS
2.
On the System Status screen, select the
3.
Press the
CONTROLS
Command screen is displayed.
4.
On the Bypass Control Command screen, select
pushbutton on the Bypass Command menu bar.
5.
Press the
SELECT
If the UPS is online, the UPS transfers to Battery mode and then to Online mode.
The Online status indicator is illuminated. The UPS status indicates ONLINE. The UPM status
indicates ONLINE.
7.6.11 Start Energy Saver System High Alert Mode from the Bypass Command Menu
To start High Alert mode:
NOTE
The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service
Engineer.
The Variable Module Management System and Energy Saver System modes are mutually exclusive. If the
Variable Module Management System mode is enabled, the Energy Saver System mode commands will not be
displayed.
1.
Press the
CONTROLS
2.
On the System Status screen, select the
3.
Press the
CONTROLS
screen is displayed.
4.
On the Bypass Control Command screen, select
5.
Press the
pushbutton on the Bypass Command menu bar.
SELECT
If the UPS is online, the UPS starts High Alert mode with the UPMs online supplying the critical load.
After one hour the UPS transfers to Energy Saver System mode.
The Online status indicator is illuminated. The UPS status indicates HIGH ALERT. The UPM
status indicates ONLINE. The power module is on.
pushbutton on the main menu bar. The System Status screen is displayed.
BYPASS
pushbutton on the System Status menu bar. The Bypass Control
pushbutton on the main menu bar. The System Status screen is displayed.
BYPASS
pushbutton on the System Status menu bar. The Bypass Control Command
9395P 250 kVA / 275 kVA / 300 kVA
User's and Installation Guide
command.
DISABLE ENERGY SAVER
command.
.
START HIGH ALERT
.
132