System Register Area - Emerson Rosemount 2460 Reference Manual

System hub for tank gauging systems
Hide thumbs Also See for Rosemount 2460:
Table of Contents

Advertisement

Reference Manual
00809-0100-2460, Rev DB
F.4.2

System Register Area

Table F-5. System Register Area
Register
Register Name
Number
2460 Status Register Area
24000
Device Status
24002
Device Error
24004
Device Warning
24006
Device Operation Mode
®
Modbus
Standard Question
Type
Unit
DWORD
Bitfield
DWORD
Bitfield
DWORD
Bitfield
WORD
Enum
®
Modbus
Standard Question
Description
Priority 5 question. Defines the unit for
the values in the FC04 area.
Priority 1 question
Bit 0: Simulation Mode Active
Bit 1: Device Warning
Bit 2: Device Error
Bit 3: SW Write Protection Active
Bit 4: HW Write Protection Active
Bit 10: Redundant System
Bit 11: Redundant Primary Device
Bit 12: Redundant Active Device
Bit 0: Firmware Error
Bit 1: CDB Error
Bit 7: IPC Error
Bit 14: SW Error
Bit 17: Internal System Error
Bit 18: License Error
Bit 0: Firmware Warning
Bit 1: CDB Warning
Bit 4: Redundancy Warning
Bit 5: Modem Warning
Bit 14: Battery Warning
Bit 15: USB Warning
Bit 16: SD-Card Warning
Bit 17: Internal System Warning
Bit 18: License Conflict
0 = Full Mode
1 = Warning Mode
2 = Error Mode