Miscellaneous control register

Use holding register Sakura_MiscControl (1210) to set some optional configuration bits, see
Enable/disable MiscCtrl configuration bits
all tank positions.
Table 5-6: Holding Register Sakura_MiscControl 1210
Bit
0
1
2
3
4
5
6
8
9
(1)
Note that this bit is only valid for the Sakura V1 protocol.
(2)
Note that the tank hub must be restarted or the Sakura bus communication must be
idle for at least one minute.
(3)
Note that this bit is only valid for the Sakura MDP protocol.
Emerson.com/Rosemount
Name
Level mapping signed
Non Standard Error Status 0x0
Invalid Temp As Sensor
Error
Device Error As Under
Tension
Device Error As Over
Tension
Invalid Level As Under
Tension
Enable Digital Relay Status 0x0
Enable MML Diagnostics
Enable SINGLE MDP RESP
Optional configuration and settings
and
Table
5-6. This configuration is applicable on
Default
Description
value
0x0
The level range is by default 0.0 - 99999.9 mm. By
setting bit 0, the level range is changed to -49999.9 -
50000 mm.
(1)
The error status value range is by default 0x30 - 0x33.
By setting bit 1, the error status value range is changed
to 0x40 - 0x43.
(1)
0x0
By setting bit 2, invalid temperature will be indicated as
error status "Sensor error".
0x0
By setting bit 3, device error will be indicated as error
status "Under Tension", Note that this error status will
overwrite both "Over tension" and "Sensor error".
0x0
By setting bit 4, device error will be indicated as error
status "Over Tension". Note that if bit 3 is set, bit 4 will
have no impact.
0x0
By setting bit 5, invalid level will be indicated as error
status "Under tension". Note that if this bit is not set,
the invalid level will be indicated as "Over tension".
By setting bit 6, the state of the relay inputs K1 and
K2 (energized or deenergized) can be read from the
Sakura V1 Digital Status byte for some responses. See
Digital input
for more information.
0x0
This is an advanced feature that can be used during
maintenance. By setting bit 8, the modem will send
up diagnostic info that can be read through the
tank hub input registers. Since this may affect the
normal operation of the Sakura emulation, it is not
recommended to use this feature, except during
maintenance.
(2)
0x0
Advanced feature that should normally not be used
except during testing. By setting bit 9, the host can
only clock out one response message compared to the
default three identical responses.
August 2023