Logging - Emerson Rosemount 2460 Reference Manual

System hub for tank gauging systems
Hide thumbs Also See for Rosemount 2460:
Table of Contents

Advertisement

Reference Manual
00809-0100-2460, Rev DB
6.9

Logging

Via a Web browser you may setup the Rosemount
all field and host ports. Log files are stored on a SD card or a USB stick.
To setup a communication log:
1. Install a USB stick or a SD card. See
2. Open the Web interface for the Rosemount 2460 System Hub. See
page 108
3. Select the Communication>Logging menu option.
4. Enable ports to be logged by checking the corresponding box.
For Modbus TCP, select the desired client. You can log one client at a time.
5. Specify Max file size and Max number of log files. It is recommended to set "Max number of log
files" to two or more. Then you can combine these two parameters to avoid that a file is overwritten.
6. Specify log destination USB or SD card. The log files will be stored in a folder named "comlogs". File
names will be given by the following syntax:
Port logging: "ComLog_Port<1-8>_<01-10>.txt".
Modbus TCP client: "ComLog_Client1_01.txt".
Examples
"ComLog_Port2_03.txt" refers to the third log file for communication port number 2.
"ComLog_Client1_02.txt" refers to the second log file for Client 1.
Service and Troubleshooting
for more information.
2460 System Hub for logging the communication on
Figure 2-5 on page 11
for information on where to connect.
Service and Troubleshooting
"Using the web interface" on
March 2017
111