Emerson Rosemount 2460 Reference Manual page 79

System hub for tank gauging systems
Hide thumbs Also See for Rosemount 2460:
Table of Contents

Advertisement

Reference Manual
00809-0100-2460, Rev DB
Single tank with a single Rosemount 2410 Tank Hub
In this example a Rosemount 2460 System Hub is connected to two tanks each of which has a separate
Rosemount 2410 Tank Hub. Each tank has a Rosemount 5900S Radar Level Gauge Radar Level Gauge, a
Rosemount 2240S Multi-Input Temperature Transmitter, and a Rosemount 2230 Graphical Field Display.
The Modbus address configuration is summarized in
Table 4-6. Example of Modbus address configuration for Rosemount 2410 Tank Hubs and
Tank
TK-1
TK-2
Figure 4-3. Configuration example of a Rosemount Tank Gauging system with a Rosemount 2460
Rosemount 2460 System Hub
For each tank, the Level Device address in the Tank Database of the Rosemount 2460 System Hub must
be equal to the Level Modbus address in the Rosemount 2410 tank database.
The Temperature Device address in the tank database of the Rosemount 2460 System Hub must be
equal to the ATD Modbus address in the tank database of the Rosemount 2410 Tank Hub.
Configuration
connected devices on two tanks
Rosemount 2410
Tank Hub
101
102
System Hub connected to two tanks each of which has a Rosemount 2410 Tank Hub
Rosemount
2410 Tank Hub
Rosemount
2410 Tank Hub
Table
4-6:
Rosemount 5900S
Level Gauge
Modbus Address
1
2
Rosemount 5900S
Level Gauge
Rosemount 2230
Field Display
TK-1
Rosemount 5900S
Level Gauge
Rosemount 2230
Field Display
TK-2
Configuration
ATD (2230, 2240S)
101
102
Rosemount 2240S
Temperature Transmitter
Rosemount 2240S
Temperature Transmitter
March 2017
69