Configuration
March 2017
In the tank database of the Rosemount 2410 Tank hub, the Rosemount 2240S temperature transmitter
and the Rosemount 2230 display are grouped into an Auxiliary Tank Device (ATD). The ATD Modbus
address has to be stored in the Temperature Device address field in the tank database of the Rosemount
2460 System Hub as illustrated in
also be stored in both the 2410 and the 2460 tank databases.
Figure 4-6. The Tank Database of the Rosemount 2460 System Hub must match the tank databases of connected
Rosemount 2410 Tank Hubs
Tank Database for a Rosemount 2410 Tank Hub that serves three tanks
Note that in this example a single Rosemount 2410 Tank Hub serves three tanks. The tanks are mapped
to tank position 1, 2, and 3 in the Rosemount 2410 Tank Hub's tank database.
In the tank database of the Rosemount 2460 System Hub, you will have to configure 2410 Tank Position in
order to be able to configure the correct Temperature Device Addresses for the three tanks.
72
Figure 4-6 on page
72. The Modbus addresses of the level devices must
Level device address
Rosemount 2460 System Hub
Reference Manual
00809-0100-2460, Rev DB
Auxiliary Tank Device (ATD) address
Configuration