Fc03 Register Area; System Register Area - Emerson Rosemount 2460 Reference Manual

System hub for tank gauging systems
Hide thumbs Also See for Rosemount 2460:
Table of Contents

Advertisement

®
Modbus
Standard Question
March 2017
F.3

FC03 Register Area

Read Holding Register.
F.3.1

System Register Area

Table F-3. System Register Area
Register
Register Name
Number
Unit Register Area
100
Level Unit
101
Level Rate Unit
102
Temperature Element Unit
103
Temperature Unit
104
Pressure Unit
176
Type
Unit
WORD
Enum (m)
WORD
Enum (m/h)
WORD
Enum (1/10°)
WORD
Enum (°C)
WORD
Enum (barG)
Reference Manual
00809-0100-2460, Rev DB
Description
Priority 5 question. Defines the unit for
values in the FC04 area.
44 = ft
45 = m (default)
120 = m/h (default)
247 = ft/h
1 = 1/10 ° (default)
2 = 1/100 °
Resolution for the value, the
Temperature Unit below will be used
32 = °C (default)
33 = °F
11 = Pa
12 = kPa
262 = psi A
263 = bar A
518 = psi G
519 = bar G (default)
239 = mm H2O
Modbus
®
Standard Question

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents