Troubleshooting
0 The serial port cannot be initialized. Serious hardware
failure
256 The power EEPROM data is defect or too old
512 The control board EEPROM data is defect or too old
513 Communication time out Reading EEPROM data
514 Communication time out Reading EEPROM data
515 The Application Orientated Control cannot recognize the
EEPROM data
516 Cannot write to the EEPROM because a write command
is on progress
517 The write command is under time-out
518 Failure in the EEPROM
519 Missing or invalid BarCode data in EEPROM 1024-1279
CAN telegram cannot be sent. (1027 indicate a possible
hardware failure)
1281 Digital Signal Processor flash time-out
1282 Power micro software version mismatch
1283 Power EEPROM data version mismatch
1284 Cannot read Digital Signal Processor software version
1299 Option SW in slot A is too old
1300 Option SW in slot B is too old
1315 Option SW in slot A is not supported (not allowed)
1316 Option SW in slot B is not supported (not allowed)
1536 An exception in the Application Orientated Control is
registered. Debug information written in LCP
1792 DSP watchdog is active. Debugging of power part data
Motor Orientated Control data not transferred correctly
2049 Power data restarted
2315 Missing SW version from power unit
2816 Stack overflow Control board module
2817 Scheduler slow tasks
2818 Fast tasks
2819 Parameter thread
2820 LCP stack overflow
2821 Serial port overflow
2822 USB port overflow
3072-
Parameter value is outside its limits. Perform an initiali-
5122
zation. Parameter number causing the alarm: Subtract
the code from 3072. Ex Error code 3238: 3238-3072=166
is outside the limit
5123 Option in slot A: Hardware incompatible with Control
board hardware
5124 Option in slot B: Hardware incompatible with Control
board hardware
5376-
Out of memory
6231
ALARM 39, Heatsink sensor
No feedback from the heatsink temperature sensor.
The signal from the IGBT thermal sensor is not available on
the power card. The problem could be on the power card,
on the gate drive card, or the ribbon cable between the
power card and gate drive card.
MG04F402
Operating Guide
WARNING 40, Overload of Digital Output Terminal 27
Check the load connected to terminal 27 or remove short-
circuit connection. Check parameter 5-00 Digital I/O Mode
and parameter 5-01 Terminal 27 Mode.
WARNING 41, Overload of Digital Output Terminal 29
Check the load connected to terminal 29 or remove short-
circuit connection. Check parameter 5-00 Digital I/O Mode
and parameter 5-02 Terminal 29 Mode.
ALARM 45, Earth fault 2
There is a discharge from the output phases to earth,
either in the cable between the frequency converter and
the motor or in the motor itself. Turn off the frequency
converter and remove the earth fault. This alarm is
detected under the start-up test sequence.
ALARM 46, Power card supply
The supply on the power card is out of range.
There are three power supplies generated by the switch
mode power supply (SMPS) on the power card: 24 V, 5 V,
+/-18 V. When powered with 24 V DC with the MCB 107
option, only the 24 V and 5 V supplies are monitored.
When powered with three-phase mains voltage, all three
phases supplied are monitored.
WARNING 47, 24 V supply low
The external 24 V DC backup power supply may be
overloaded, otherwise Contact your Danfoss supplier.
WARNING 48, 1.8 V supply low
Contact your Danfoss supplier.
WARNING 49, Speed limit
The speed is not within the specified range in
parameter 4-11 Motor Speed Low Limit [RPM] and
parameter 4-13 Motor Speed High Limit [RPM].
ALARM 50, AMA calibration failed
The motor is not suitable for the particular size of drive.
Start the AMA procedure once again by
parameter 1-29 Automatic Motor Adaptation (AMA),
eventually with a reduced AMA function. If still failing;
check the motor data.
ALARM 51, AMA check Unom and Inom
The setting of motor voltage, motor current, and motor
power is presumably wrong. Check the settings.
ALARM 52, AMA low Inom
The motor current is too low. Check the settings.
ALARM 53, AMA motor too big
The motor is too large for the AMA to be carried out.
ALARM 54, AMA motor too small
The motor is too small for the AMA to be carried out.
ALARM 55, AMA par. out of range
The motor parameter values found from the motor are
outside acceptable range.
ALARM 56, AMA interrupted by user
The AMA has been interrupted by the user.