Dip Switches; Serial Communication; Connection To Pc - Danfoss VLT Decentral Drive FCD 302 Operating Manual

Hide thumbs Also See for VLT Decentral Drive FCD 302:
Table of Contents

Advertisement

Installation
1
2
Min. 16 mm
(4 AWG)
2
Equalizing conductor

2.4.13 DIP Switches

Analog input terminals 53 and 54 can select for
either voltage (0-10 V) or current (0-20 mA) input
signals.
Set switches S201 (terminal 53) and S202
(terminal 54) to select the signal type. ON is for
current, OFF for voltage.
Terminal 53 default is for a speed reference in
open loop.
Terminal 54 default is for a feedback signal in
closed loop.
3
1
S201 - terminal 53
2
S202 - terminal 54
3
S801 - standard bus termination
4
Profibus termination
5
Fieldbus address
Illustration 2.25 Location of DIP Switches
NOTICE
Switches 4 and 5 are only valid for units fitted with
fieldbus options.

2.4.14 Serial Communication

Connect RS485 serial communication wiring to terminals
(+)68 and (-)69.
Switch S801 (BUS TER.) can be used to enable
termination on the RS485 port (terminals 68 and
69). See Illustration 2.25.
Shielded serial communication cable is
recommended
See chapter 2.4.11 Earth (Grounding) Requirements
for proper grounding
MG04F402
Operating Guide
1
2
4
5
Danfoss A/S © 05/2016 All rights reserved.
Two communication protocols are internal to the
frequency converter
-
Danfoss FC
-
Modbus RTU
For basic serial communication setup, select the
following
-
Protocol type in parameter 8-30 Protocol
-
Frequency converter address in
parameter 8-31 Address
-
Baud rate in parameter 8-32 Baud Rate
Functions can be programmed remotely using
the protocol software and RS485 connection or in
parameter group 8-** Communications and Options
Selecting a specific communication protocol
changes various default parameter settings to
match that specifications of the protocol along
with making additional protocol-specific
parameters available
Control card options are available to provide
additional communication protocols. See the
option-card documentation for installation and
operation instructions
-
PROFIBUS
-
Ethernet IP
-
PROFINET

2.4.15 Connection to PC

To control the frequency converter from a PC, install the
MCT 10 Set-up Software.
The PC is connected via a standard (host/device) USB
cable, or via the RS485 interface.
Illustration 2.26 Electronic Part
2
2
25