Status Indication
Jogging
Motor check
6
6
OVC Control
Power Unit Off
Protection md
QStop
Ramping
Ref. high
Ref. low
62
VLT
The motor is running as programmed in
parameter 3-19 Jog Speed [RPM].
Jog was selected as function for a digital
input (parameter group 5-1* Digital Inputs).
The corresponding terminal is active.
The jog function is activated via the serial
communication.
The jog function was selected as a reaction
for a monitoring function. The monitoring
function is active.
In parameter 1-80 Function at Stop, Motor
Check was selected. A stop command is active.
To ensure that a motor is connected to the
frequency converter, a permanent test current
is applied to the motor.
Overvoltage control was activated in
parameter 2-17 Over-voltage Control, [2]
Enabled. The connected motor supplies the
frequency converter with generative energy.
The overvoltage control adjusts the V/Hz ratio
to run the motor in controlled mode and to
prevent the frequency converter from tripping.
(Only frequency converters with a 24 V
external supply installed).
Mains supply to the frequency converter is
removed, but the control card is supplied by
the external 24 V.
Protection mode is active. The unit has
detected a critical status (an overcurrent or
overvoltage).
To avoid tripping, the switching frequency
is reduced to 4 kHz.
If possible, protection mode ends after
approximately 10 s.
Protection mode can be restricted in
parameter 14-26 Trip Delay at Inverter Fault.
The motor is decelerating using
parameter 3-81 Quick Stop Ramp Time.
Quick stop inverse was selected as a
function for a digital input (parameter
group 5-1* Digital Inputs). The
corresponding terminal is not active.
The quick stop function was activated via
serial communication.
The motor is accelerating/decelerating using
the active ramp up/down. The reference, a
limit value, or a standstill is not yet reached.
The sum of all active references is above the
reference limit set in parameter 4-55 Warning
Reference High.
The sum of all active references is below the
reference limit set in parameter 4-54 Warning
Reference Low.
Danfoss A/S © 05/2016 All rights reserved.
®
Decentral Drive FCD 302
Run on ref.
Run request
Running
Sleep Mode
Speed high
Speed low
Standby
Start delay
Start fwd/rev
Stop
Trip
Trip lock
Table 6.4 Operation Status
NOTICE
In auto/remote mode, the frequency converter requires
external commands to execute functions.
The frequency converter is running in the
reference range. The feedback value matches
the setpoint value.
A start command has been given, but the
motor is stopped until a run permissive signal
is received via digital input.
The frequency converter drives the motor.
The energy saving function is enabled. The
motor has stopped, but restarts automatically
when required.
Motor speed is above the value set in
parameter 4-53 Warning Speed High.
Motor speed is below the value set in
parameter 4-52 Warning Speed Low.
In Auto On mode, the frequency converter
starts the motor with a start signal from a
digital input or serial communication.
In parameter 1-71 Start Delay, a delay starting
time was set. A start command is activated
and the motor starts after the start delay time
expires.
Start forward and start reverse were selected
as functions for 2 different digital inputs
(parameter group 5-1* Digital Inputs). The
motor starts in forward or reverse depending
on which corresponding terminal is activated.
The frequency converter has received a stop
command from the LCP, digital input, or serial
communication.
An alarm occurred and the motor is stopped.
Once the cause of the alarm is cleared, the
frequency converter can be reset manually by
pressing [Reset] or remotely by control
terminals or serial communication.
An alarm occurred and the motor is stopped.
Once the cause of the alarm is cleared, power
must be cycled to the frequency converter.
The frequency converter can then be reset
manually by pressing [Reset] or remotely by
control terminals or serial communication.