Generator paralleling controller
Hide thumbs Also See for GPC-3:
Table of Contents

Advertisement

GPC-3 DRH 4189340587 UK
Temperature
°C
°F
40
104
50
122
60
140
70
158
80
176
90
194
100
212
110
230
120
248
130
266
140
284
150
302
The configurable type is configurable with eight points in the range 0 to 480 Ω. The tempera-
ture as well as the resistance can be adjusted.
If the RMI input is used as a level switch, then be aware that voltage must not be connected to
the input. If any voltage is applied to the RMI input, it will be damaged. Refer to the Application
Notes for further wiring information.

4.6.7 RMI fuel

This RMI input is used for the fuel level sensor.
Value
0 %
100 %
Value
0 %
100 %
If the RMI input is used as a level switch, then be aware that voltage must not be connected to
the input. If any voltage is applied to the RMI input, it will be damaged. Refer to the Application
Notes for further wiring information.
DEIF A/S
RMI sensor
type
Type 1
Type 2
291.5
480.7
197.3
323.6
134.0
222.5
97.1
157.1
70.1
113.2
51.2
83.2
38.5
62.4
29.1
47.6
22.4
36.8
28.9
22.8
18.2
RMI sensor type
Type 1
Resistance
78.8 Ω
1.6 Ω
RMI sensor type
Type 2
Resistance
3 Ω
180 Ω
Type 3
Type 4
69.3
36.0
19.8
Type 4 is not available when RMI
water is selected
11.7
7.4
Additional functions
Page 45 of 122