Connecting Terminal Resistors; Terminal Block; Terminal Resistor Type; When Using The Fx - Mitsubishi FX3U-232-BD User Manual

Fx3u series
Hide thumbs Also See for FX3U-232-BD:
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
N:N Network

2. Terminal block

In the FX
-485ADP and FX-485ADP, the terminal screw size is "M3".
0N
Make sure to use a crimp-style terminal with the following sizes.
Make sure that the tightening torque is 0.5 to 0.8 N·m.
• When wiring one cable to one terminal
6.2 mm (0.24")
or less
6.2 mm (0.24")
or less
• When wiring two cables to one terminal
6.2 mm (0.24")
or less
6.2 mm (0.24")
or less
4.2.3

Connecting terminal resistors

Make sure to provide a terminal resistor at the end of each line.
In the case of one-pair wiring, connect a terminal resistor to the RDA-RDB signal
terminal of the communication equipment.

1. Terminal resistor type

Use two terminal resistors of 110 Ω, 1/2 W.
Among the terminal resistors supplied with the communication equipment, select
ones with the color codes shown to the right.

2. When using the FX

The FX
-485-BD and FX
3U
Set the terminal resistor selector switch accordingly.
330 Ω
OPEN
110 Ω
φ 3.2 (0.13")
6.3 mm (0.25")
or more
φ 3.2 (0.13")
Terminal
6.3 mm (0.25")
or more
φ 3.2 (0.13")
6.3 mm (0.25")
or more
φ 3.2 (0.13")
Terminal
6.3 mm (0.25")
or more
-485-BD or FX
-485ADP(-MB)
3U
3U
-485ADP(-MB) have built-in terminal resistors.
3U
Terminal
resistor selector
330 Ω
switch
OPEN
110 Ω
4.2 Selecting Cables and Terminal Resistors
Crimp-style
Terminal
terminal
screw
Terminal
Crimp-style
screw
terminal
330 Ω
OPEN
110 Ω
4 Wiring
Brown
Precision
=110 Ω
1 1 1
1
(10
)
Terminal
resistor selector
switch
Apx.
B-19
A
B
C
D
E
F
G
H
I

Advertisement

Table of Contents
loading

Table of Contents