External Dimensions; Terminal Layouts - Mitsubishi Melsec FX-4AD User Manual

Special function block
Table of Contents

Advertisement

1.1 External dimensions

-
+
I+
FG
-
COM
+
V+
DC24V
CH1
M3.5 (0.14")
terminal
screws
Extension
cable and
connector
CH2
CH3
CH4
I+
FG
FG
I+
FG
I+
V+
COM
V+
COM
V+
COM
2
CH4
Voltage input
0 to +/-10V
+
V
*2
200K
+
I
COM
*1 shielded
FG
CH1
Current input
0 to +/-20mA
+
V
+
I
*3
COM
*1 shielded
FG
*4
50mA
DC24V
+
*5
DC24V
DC24V
-
Class 3
Extension cable
Grounding
PC
(100
or less)
FX-4AD Analog Input Block
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
weight : Approx 0.5kg (1.1 lbs) Dimensions:mm (inches)
24V
A-D
+
-
I+
FG
+
-
V+
COM
DC24V
CH1
POWER
CH1
READY
CH2
CH3
125
140
CH4
(4.92")
(5.51")
OFFSET
GAIN
CH2
CH3
CH4
I+
FG
I+
FG
I+
I+
FG
FG
V+
V+
COM
COM
V+
COM
V+
COM
63 (2.48")
73 (2.87")

TERMINAL LAYOUTS

100K
*1 The analog input is received through a twisted
pair shielded cable. This cable should be wired
100K
separately from power lines or any other lines
which may induce electrical noise.
AG(analog ground)
*2 If a voltage ripple occurs during input, or there is
100K
electrically induced noise on the external wiring,
250K
connect a smoothing capacitor of 0.1 to 0.47µF,
100K
25V.
*3 If you are using current input, connect the V+ and
I+ terminals to each other.
*4 If there is excessive electrical noise, connect the
+15V
DC/DC
FG frame ground terminal with the grounded
AG
con verter
terminal on the FX-4AD.
-15V
*5 Connect the ground terminal on the FX-4AD unit
with the grounded terminal on the base unit. Use
class 3 grounding on the base unit, if available.
35mm
(1.38in.)
DIN rail
mounting
slot
Mounting
holes
5.5mm
(0.27in.)
dia.
10 (0.39")
95 (3.74")

Advertisement