FX Series PLC User's Manual - Data Communication Edition
Programming Communication
2.3
Caution on Selection
Some caution should be observed when using a programming tool with optional FX PLC communication
equipment.
Consider the following contents during selection.
2.3.1
When using 422BD
1. Current consumption at 5V DC of the expansion board
When the 422BD is attached to a PLC, it consumes the following current:
1) For FX
and FX
3U
The FX
-422-BD consumes 20 mA at 5V DC from the FX
3U
2) For FX
PLCs
2N
The FX
-422-BD consumes 60 mA at 5V DC from the FX
2N
2. Current consumption of the special extension equipment and peripheral equipment
Make sure that the current consumption at 5V DC including the 422BD described above, special extension
equipment, and peripheral equipment shown below does not exceed the power capacity at 5V DC in the
FX
/FX
/FX
2N
3U
Peripheral equipment
FX-20P(-E)
FX-10P(-E)
Personal computer
(for programming)
FX-10DU(-E)
FX-20DU(-E)
FX-10DM(-E)
FX-25DU(-E), FX-30DU(-B)(-E),
FX-40DU(-B)(-ES), FX-40DU-TK(B)(-E),
FX-50DU-TK(S)(-E), and ET-50 Series
F940GOT-SWD(LWD)(-E),
F930GOT-BWD(-E), ET-940 Series
F930GOT-BBD-K(-E), and F920GOT-BBD-K
F940 Handy GOT (RH type)
F920GOT-BBD5-K
F920 Handy GOT RH type
GOT-A900 Series
(CPU direct connection type)
GOT1000 Series
(CPU direct connection type)
*1.
The power consumption of the FX
H-16
PLCs
3UC
PLC.
3UC
/FX
3U
PLC.
2N
Connection cable
FX-20P-CAB0 or FX-20P-CAB + FX-20P-CADP
<F
-232CAB (for 25-pin D-Sub),
2
F
-232CAB-1 (for 9-pin D-Sub) or
2
F
-232CAB-2 (for 14-pin half-pitch)>
2
+ FX-232AW(C) + FX-422CAB0
<F
-232CAB (for 25-pin D-Sub),
2
F
-232CAB-1 (for 9-pin D-Sub) or
2
F
-232CAB-2 (for 14-pin half-pitch)>
2
+ FX-232AWC-H + FX-422CAB0
USB cable
(for connecting personal computer: A plug, male type)
(for connecting FX-USB-AW: MINI B plug, male type)
+ FX-USB-AW
FX-20P-CAB0 or FX-20P-CAB + FX-20P-CADP
FX-20DU-CAB0
FX-20P-CAB0 or FX-20P-CAB + FX-20P-CADP
FX-50DU-CAB0(-1M, -10M, -20M, -30M)
FX-40DU-CAB(-10M, -20M, -30M) + FX-422AW0
FX-50DU-CAB0(-1M, -10M, -20M, -30M, L)
F9GT-H(RH)CAB2-150 + F9GT-H(RH)CAB-3M(-10M)
or F9GT-HCAB-3M(-10M) + F9GT-HCNB + FX-50DU-
CAB0(-1M)
FX-50DU-CAB0(-1M)
F9GT-HCAB2-150, F9GT-HCAB-3M(-10M)
FX9GT-CAB0(-150,-10M)
GT01-C R4-8P
(Where
represents 10, 30, 100, or 300.)
-422-BD and FX
-422-BD is not included.
3U
2N
2 System Configuration and Selection
2.3 Caution on Selection
-32MT-LT PLC.
3UC
Current
consumptio
*1
n at 5V DC
180 mA
120 mA
220 mA
120 mA
15 mA
220 mA
180 mA
220 mA
0 mA
160 mA
0 mA
0 mA
220 mA
0 mA
0 mA