FX Series PLC User's Manual - Data Communication Edition
N:N Network
7.4

Cautions on Program Creation

1. Effect on the operation cycle

When the N:N Network is used, the operation cycle in each PLC becomes longer by about 10% regardless of
the number of linked stations and adopted communication patterns.
2. Program for setting the N:N Network
1) Make sure to create a program for setting the N:N Network from step 0 using M8038 (drive contact).
Otherwise, the N:N Network is disabled.
2) Do not set M8038 to ON using a program or programming tool.
3) Set station numbers consecutively. If a station number that is used twice or more is skipped, link will not
be achieved normally.
3. Program for reading link devices
Do not change the contents of link devices at other stations.
1) When a link error (data transfer sequence error) occurs, the link device information is held in the status
just before occurrence of the link error.
Create a fail-safe program which does not cause abnormality even if a link error occurs.
4. Cautions on using FX
1) Link pattern when FX
When FX
1S
setting).
If any other pattern is set, data transfer error occurs in all FX
the link time becomes longer.
2) When user devices are occupied as system devices
In FX
/FX
1S
Network, and cannot be handled as general devices any more. Do not set these devices to ON or OFF
using a user program, display unit or programming tool.
If these devices are set to ON or OFF, the N:N Network may malfunction.
5. Cautions on using FX
1) Only ch 1 or ch 2 can be set in the N:N Network.
2) Do not use the N:N Network and parallel link at the same time.
(For example, it is not allowed to use ch1 for the N:N Network and use ch2 for parallel link.)
B-34
/FX
PLCs
1S
0N
/FX
PLCs are used or included
1S
0N
/FX
PLCs are included in the system, make sure to set pattern 0 in D8178 (refresh range
0N
PLCs, M503 to M511 and D201 to D255 are handled as devices dedicated to the N:N
0N
/FX
PLCs
3U
3UC
7.4 Cautions on Program Creation
/FX
PLCs included in the system, and
1S
0N
7 Creating Programs