FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
4.9
Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100Ω or less.
• Independent grounding should be performed for best results.
When independent grounding can not be performed, perform "shared grounding" as shown in the following
figure.
Other
PLC
equipment
Independent grounding
Best condition
• The grounding wire size should be AWG 14 (2 mm
• The grounding point should be close to the PLC, and all grounding wires should be as short as possible.
→ For details, refer to the Hardware Edition of each series.