Mitsubishi FX3U-232-BD User Manual page 192

Fx3u series
Hide thumbs Also See for FX3U-232-BD:
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
Parallel Link
7.2.3
Creating programs for slave station
Create programs for the slave station.
RUN monitor
M8000
Parallel link ON
M8072
Master/
slave station
setting error
M8073
RUN monitor
M8000
X010
RUN monitor
M8000
X010
C-42
Slave station setting
M8071
High speed parallel
link mode
M8162
Channel setting
M8178
Y010
FNC 12
K1X000
Link device
MOV
FNC 12
C0
Link device
MOV
FNC 12
Link device
K1Y000
MOV
FNC 12
Link device
D10
MOV
Program for setting the slave station
M8071 is set to ON to set a PLC as the slave station.
M8162 is set to ON to set the high speed parallel link
mode.
(In the FX
and FX
3U
When using ch 1, this step is not required.
When using ch 2, set M8178 to ON."
Program for indicating link errors
When the parallel link is interrupted or the setting is
defective, Y10 is set to ON.
Program for writing link devices (slave station → master
station)
The information on X000 to X003 is written to link
devices.
• For PLC series other than the FX
D500 and D501
• For FX
or FX
1S
0N
C0
K100
The current value of C0 is written to link devices.
• For PLC series other than the FX
D500 and D501
• For FX
or FX
1S
0N
Program for reading link devices (master station →
slave station)
The information on link devices is read to Y000 to Y003.
• For PLC series other than the FX
D490 and D491
• For FX
or FX
1S
0N
The current value of C0 is written to link devices.
• For PLC series other than the FX
D490 and D491
C1
• For FX
or FX
1S
0N
D10
7 Creating Programs
7.2 High Speed Parallel Link Mode
)
3UC
or FX
:
1S
0N
Series: D240 and D241
or FX
:
1S
0N
Series: D240 and D241
or FX
:
1S
0N
Series: D230 and D231
or FX
:
1S
0N
Series: D230 and D231

Advertisement

Table of Contents
loading

Table of Contents