Mitsubishi FX3U-232-BD User Manual page 174

Fx3u series
Hide thumbs Also See for FX3U-232-BD:
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
Parallel Link
2. Terminal block
In the FX
-485ADP and FX-485ADP, the terminal screw size is "M3".
0N
Make sure to use a crimp-style terminal with the following sizes.
Make sure that the tightening torque is 0.5 to 0.8 N·m.
• When wiring one cable to one terminal
6.2 mm (0.24")
or less
6.2 mm (0.24")
or less
• When wiring two cables to one terminal
6.2 mm (0.24")
or less
6.2 mm (0.24")
or less
4.2.3
Optical fiber cable
Two optical fiber cables are required.
1. Cable types
Cable
F-OFC-M10
F-OFC-M30
F-OFC-M50
2. Cautions on wiring
Separate the optical connector from strong electric cables as much as possible.
Connect devices with the smallest load to the output terminals Y000 to Y003 which are located near the
optical connector.
C-24
φ 3.2 (0.13")
6.3 mm (0.25")
or more
φ 3.2 (0.13")
6.3 mm (0.25")
or more
φ 3.2 (0.13")
6.3 mm (0.25")
or more
φ 3.2 (0.13")
6.3 mm (0.25")
or more
Length
10 m (32' 9")
Optical connector CA9104AP manufactured by Hitachi is already connected.
30 m (98' 5")
Optical connector CA9104AP manufactured by Hitachi is already connected.
50 m (164' 0")
Optical connector CA9104AP manufactured by Hitachi is already connected.
4.2 Selecting Cables and Terminal Resistors
Crimp-style
Terminal
terminal
screw
Terminal
Terminal
Crimp-style
screw
terminal
Terminal
Remarks
4 Wiring

Advertisement