Power Cable Connection Diagram - ABB ACS880-04 Hardware Manual

200 to 710 kw, 300 to 700 hp
Hide thumbs Also See for ACS880-04:
Table of Contents

Advertisement

Power cable connection diagram

ACS880-04
1
For alternatives, see section
example of this chapter, the disconnecting device is not in the same cubicle with the drive module.
2
If a shielded cable is used (not required but recommended) and the conductivity of the shield is
< 50% of the conductivity of the phase conductor, use a separate PE cable (2a) or a cable with a
grounding conductor (2b).
3
We recommend 360-degree grounding at the cabinet entry if a shielded cable is used. Ground the
other end of the input cable shield or PE conductor at the distribution board.
4
We recommend 360-degree grounding at the cabinet entry, see page
5
Use a separate grounding cable if the conductivity of the cable shield is < 50% of the conductivity of
the phase conductor and there is no symmetrically constructed grounding conductor in the cable
(see page 71).
(PE)
PE
(PE)
L2
L3
L1
2a
2b
3
L1
L2
L3
PE
L1/
L2/
L3/
U1
V1
W1
INPUT
OUTPUT
T1/
T2/
T3/
U2
V2
W2
4
V1
W1
U1
~
3
M
Selecting the supply disconnecting device
Installation instructions 99
1
9
UDC-
UDC+
PE
R-
R+
7
8
4
6
5
on page
51.
10
64.
In the installing