182 Technical data

Fuses (UL)

UL fuses for branch circuit protection per NEC are listed below. Check that the operating
time of the fuse is below 0.1 seconds. The operating time depends on the fuse type,
supply network impedance and the cross-sectional area, material and length of the supply
cable. The fuses must be of the "non-time delay" type. Obey local regulations.
Drive type
Input
ACS880-04-
current
(A)
U
= 400 V
N
505A-3
505
585A-3
585
650A-3
650
725A-3
725
820A-3
820
880A-3
880
U
= 460 V
N
460A-5
460
503A-5
503
583A-5
583
635A-5
635
715A-5
715
820A-5
820
880A-5
880
U
= 600 V
N
330A-7
330
370A-7
370
430A-7
430
470A-7
470
522A-7
522
590A-7
590
650A-7
650
721A-7
721
Note 1: See also
Implementing thermal overload and short-circuit protection
Note 2: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 3: Fuses with higher current rating than the recommended ones must not be used. Fuses with lower
current rating can be used.
Note 4: Fuses from other manufacturers can be used if they agree with the ratings and the melting curve of the
fuse does not exceed the melting curve of the fuse mentioned in the table.
A
V
600
600
800
600
800
600
800
600
900
600
1000
600
600
500
600
600
800
600
800
600
800
600
900
600
1000
600
500
600
500
600
500
600
600
600
600
600
800
600
800
600
800
600
Fuse
Manufacturer
UL class
Bussmann
T
Ferraz
L
Ferraz
L
Ferraz
L
Ferraz
L
Ferraz
L
Bussmann
T
Bussmann
T
Ferraz
L
Ferraz
L
Ferraz
L
Ferraz
L
Ferraz
L
Bussmann
T
Bussmann
T
Bussmann
T
Bussmann
T
Bussmann
T
Ferraz
L
Ferraz
L
Ferraz
L
on page 75.
Type
JJS-600
A4BY800
A4BY800
A4BY800
A4BY900
A4BY1000
JJS-500
JJS-600
A4BY800
A4BY800
A4BY800
A4BY900
A4BY1000
JJS-500
JJS-500
JJS-500
JJS-600
JJS-600
A4BY800
A4BY800
A4BY800