136 Installation example with full cabling panels (option +H381)
4. Attach the drive module lifting lugs to the cabinet frame with chains.
5. Push the drive module carefully into to the cabinet preferably with the help from
another person.
6. Attach the grounding busbar that has been previously attached to the input cabling
panel to the drive module. Note: The design of the grounding busbar can be different
from what is shown in the figure.
6
M8×16 Hex
7. Connect the busbars of the drive module to the busbars of the cabling panels
(M12 combi screw, 70 N·m [52 lbf·ft]).
8. Attach the drive module to the cabinet from top and bottom, see page
or page
141
(frame R11). Note: The top fastening bracket grounds the drive module to
the cabinet frame.
9. Attach the cabinet roof on the spacers and the side panels, see page 140.
10. Remove the filter mats from the air filters according to Rittal's instructions. Install the
filters to the cabinet door, see page 140.
11. Drive modules with an external control unit: Put back the removed front covers of the
drive module on the power cable sections, and connect the control cables (see section
Connecting the control cables to the terminals of the control unit
Drive modules with an internal control unit (option +P905): Connect the control cables
to the control unit (see section
(options +P905 and +0B051)
back the removed front covers of the drive module.
M8×20 Hex
Connecting the control cables to the internal control unit
on page 114), connect the control panel cable and put
138
(frame R10)
on page 107).