SUREFIRE ELECTRONIC IGNITION SYSTEM
S.I.T. PROFLAME 2 TROUBLESHOOTING
POTENTIAL CAUSES FOR FLAME SENSOR NOT TO PROVE
Venting Related Issues (See each manual for specific information relating to tested and approved venting
systems)
•
Partial Intake Liner - intake and exhaust liners must be of approved size and run continuous to termination
•
Unapproved Termination
•
Unapproved Vent Configuration
•
Enclosed Termination
•
Incorrect Vent Restrictor Setting
•
Crossed Liners
•
Silicone sealant used on venting.
•
If Liners have large sags, pull liners tight and keep run as straight as possible
Gas Supply Issues (See each units manuals for required pressure)
•
Ensure Sediment Trap (Drip Leg) is installed in supply line prior to the gas valve.
•
Measure static and working pressures on inlet and outlet taps
•
Measure Outlet Gas Pressure with unit ON(call for heat)
•
If inlet working pressure is to low check for blockage or incorrect gas line size
If outlet working pressure is incorrect and inlet pressure is correct check the following:
•
Converted Units - verify adherence to proper conversion instructions
•
Cold Vents/ Cold Start - unit may need to be cycled again to overcome the cold vent/cold start
•
Turn unit OFF, then back ON to cycle the unit again
•
Misplaced logs/glass or stone - check manual for correct certified media placement
SimTech Proflame II
41