A.3.14
Communication settings with the function codes 0x03, 0x04, and 0x10
Addressing the communication settings
Table A- 22
Communication settings
Offset
Number
Name
of
registers
63001
2
IP Address
63003
2
Subnetmask
63005
2
Gateway
63007
2
Bootloader Version
63009
2
Password Protection
ON/OFF
63011
2
Manufacturing Date
63015
2
Ethernet Protocol
63017
2
Protocol Module
Interface 1
63019
2
Address Module
Interface 1
63021
2
Baudrate Module
Interface 1
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
Format
Unit
Unsigned
-
long
Unsigned
-
long
Unsigned
-
long
Unsigned
-
long
Unsigned
-
long
Unsigned
-
long
Unsigned
-
long
Unsigned
-
long
Unsigned
-
long
Unsigned
-
long
Applicable
Value range
MODBUS
function
codes
0x03
•
0 ... FFFFFFFFh
0x04
•
0x10
•
0x03
•
0 ... FFFFFFFFh
0x04
•
0x10
•
0x03
•
0 ... FFFFFFFFh
0x04
•
0x10
•
0x03
•
char, uchar,
uchar, uchar
0x04
•
0x03
•
0 =
OFF
0x04
•
1 =
ON
0x03
•
[Date information]
0x04
•
0x10
•
0x03
•
0 =
MODBUS T
CP
0x04
•
1 =
SEAbus TC
0x10
•
P
0x03
•
0 =
MODBUS T
CP
0x04
•
1 =
SEAbus
0x10
•
serial
2 =
Gateway
0x03
•
1 ... 247
0x04
•
0x10
•
0x03
•
0 =
4800 baud
0x04
•
1 =
9600 baud
0x10
•
2 =
19
200 baud
3 =
38
400 baud
Appendix
A.3 MODBUS
Access
RW
RW
RW
R
R
R
RW
RW
RW
RW
237