7.3.3

Date and time

First, set the time zone and summertime. Then enter the date and time of day.
Note
Correct time measurement urgently requires specification of the time zone and a change of
time from normal to summertime.
The time zone refers to coordinated universal time (UTC).
"TIME ZONE" examples:
● Value "-06:00" corresponds to UTC-6
● Value "+01:00" corresponds to UTC+1
Procedure
1. Exit the measured value display and call the "MAIN MENU":
<F4>
2. In the main menu, go to the "SETTINGS" entry:
<F2>
3. Call the "SETTINGS" entry:
<F4>
4. In the "SETTINGS" menu, go to the "DATE/TIME OF DAY" entry:
<F2>
Figure 7-3
5. Call the "DATE/TIME OF DAY" entry:
<F4>
The display shows the currently valid settings.
6. Go to the fields "DATE", "FORMAT", "TIME", "TIME ZONE", "DAYLIGHTSAVING":
<F2>
7. Open edit mode of the device setting:
<F4>
8. Set the correct value:
<F2>
9. Accept the value with:
<F4>
The value is permanently saved and becomes effective immediately.
The display returns to display mode.
10. Return to one of the selection menus or to the measured values display:
<F1>
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
or <F3>
or <F3>
"DATE/TIME" device settings
or <F3>
and <F3>
,
.
Startup
7.3 Parameterizing the device
89