Technical data
11.1
Technical data
Device configuration
● 2 slots for up to 2 optional expansion modules
● 2 opto-isolated digital inputs with one shared terminal
● 2 opto-isolated digital outputs with one shared terminal
● 1 Ethernet interface, RJ45 socket for connecting to the PC or network
Measurement
Only for connection to AC voltage systems
Measuring method
For voltage measurement
for current measurement
Measured value acquisition
Energy
Current, voltage
Waveform
Frequency of the relative fundamental
Measured value acquisition mode
Measuring inputs for voltage
Device with wide-voltage power supply
Voltage ph-n
Voltage ph-ph
Min. measurable voltage
Impulse withstand voltage
Measuring category
Input resistance (ph-n)
Power consumption per phase
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
Voltage ph-n
Voltage ph-ph
Input voltage V
I
True root-mean-square measurement (TRMS)
True root-mean-square measurement (TRMS)
Contiguous (zero blind measuring)
Contiguous (zero blind measuring)
Settable refresh time for values on the display: 330 to
3000 ms
Sinusoidal or distorted
50 / 60 Hz
Automatic mains frequency acquisition
3~ 400 V AC (+ 20 %), max. 347 V for UL
3~ 690 V AC (+ 20 %), max. 600 V for UL
AC 3~ 57 V – 80%
AC 3~ 100 V – 80%
> 9.5 kV (1.2/50 μs)
(in accordance with IEC/UL 61010 Part 1)
CAT III
1.05 Mohms
Max. 220 mW
11
153