Modbus communication parameters with the function codes 0x03, 0x04
and 0x10
Addressing the communication parameters
Table A- 9
Addressing the communication parameters
Offset
Number of
Name
registers
63019
2
ModbusRTU address
63021
2
ModbusRTU baud rate
63023
2
ModbusRTU data bits/parity/stop
bits
63025
2
ModbusRTU response time
Addressing the settings for the I&M data
Table A- 10
Addressing the settings for the I&M data
Offset
Number of
Name
registers
64001
27
I&M 0 data
64028
89
I&M 1 data ... I&M 4 data
PAC1020
Equipment Manual, 05/2020, L1V30610008B-01
Format
Unit
unsigned long
unsigned long
unsigned long
unsigned long
ms
Format
stIM0
stIM14
A.1 Modbus
Value range from
... to
1 ... 247
0 ... 5
0 = 4800 baud
1 = 9600 baud
2 = 19200 baud
3 = 38400 baud
4 = 57600 baud
5 =
115200 baud
0 ... 3
0 = 8N2
1 = 8E1
2 = 8O1
3 = 8N1
0 ... 255
Applicable Modbus
Access
function codes
R
0x03
0x04
RW
0x03
0x04
0x10
Appendix
Access
RW
RW
RW
RW
87